I/O modules PCD1|PCD2
Digital output modules, electrically isolated
5
5.5
Digital output modules, electrically isolated
PCD2.A200
4 make contacts 2 A, 250 V
AC
| 50 V
DC
PCD2.A210
4 break contacts 2 A, 250 V
AC
| 50 V
DC
PCD2.A220
6 make contacts 2 A, 250 V
AC
| 50 V
DC
PCD2.A250
8 make contacts 2 A, 48 V
AC
| 50 V
DC
pluggable 14-pole screw terminal block
PCD2.A410
8 digital outputs 0.5 A each, 5…32 V
DC
,
electrically isolated against PCD2 bus
Installation instructions
For reasons of safety it is not permissible to connect low voltages (up to 50 V) and
higher voltages (50 … 250 V) to the same module.
If a Saia PCD
®
module is connected to a higher voltage (50 … 250 V), approved
components for this voltage must be used for all elements that are electrically con-
nected to the system.
Using higher voltage (50 … 250 V), all connections to the relay contacts must be
connected on the same circuit, i.e. in such a way that they are all protected against
one AC phase by one common fuse. Each load circuit may also be protected
individually.
I/O modules and I/O terminal blocks may only be plugged in and removed when
the Saia PCD
®
and the ex24 V are disconnected from the power supply.
In the appendix, Chapter A.4 relay contacts, are calculation data and wiring sug-
gestions for the relay contacts. These data should be absolutely considered for
safe switching and a long life span of the relays.