Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
9-4
PCD2.G200
Specifications
9
Technical data
ANALOGUE INPUTS
Number of inputs
8
Confiquration
AI0 / AI1:
AI2 / AI3 / AI4 / AI5:
AI6 / AI7:
0…10 V
Dip Switch selectable
PT/NI1000
Galvanic separation
no
Signal ranges
0…10 V Resolution*) 2.44 mV
0…20 mA, Resolution*) 4.88 μA
*) Resolution = value of least significant bit (LSB)
Resolution (digital representation)
12 bits (0…4095) rsp. directly in 1/10 °C or in 0.1 Ω
Connection technique for sensors
2-wires (passiv input)
Measuring principle
Single ended
Input resistance
10 V range:
20 mA range:
PT/NI1000:
20 kΩ
125 Ω
7.5 kΩ
Input filter
typ.
typ.
10 ms (0…10 V)
20 ms (0…20 mA; PT/NI1000)
Input ranges for temperature sen-
sors
PT1000:
NI1000:
NI1000L&S:
Resistance:
Resistance:
–
50…+400°C
–
60…+200°C
–
60…+200°C
0 … 2500 Ω
0 … 300 kΩ
Accuracy at 25°C
± 0.5% (±0.4% ±4 LSB)
Temperature error (0…+55°C)
± 0.25%
Overrange protection
10 V range: + 35 V (39 V TVS Diode)
20 mA range: no protection ( 40 mA max.)
Terminals
1 plug-in spring-load terminal block, 10-pole,
3.5 mm for wiring up to 1 mm
2
, orange
ANALOGUE OUPUTS
Number of outputs
8
Galvanic separation
no
Signal ranges
0…10 V Resolution 10 mV, LSB (least significant bit)
Resolution (digital representation)
10 bits (0…1023)
Accuracy at 25°C
± 0.5% ± 50 mV
Temperature error (0…+55°C)
± 0.25%
Load resistance
min. 3 kΩ
Short-circuit protection
yes, permanent
Terminals
1 plug-in spring-load terminal block, 10-pole,
3.5 mm for wiring up to 1 mm
2
, orange
Table 2:
Technical data of the module