Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-131
I/O modules PCD1|PCD2
PCD2.H32x
5
Encoder inputs for modules PCD2.H320 and PCD2.H322
Axis 1
Axis 2
Inputs
A B IN
A B IN
Number of inputs
3
3
Input voltage (typical)
24 V
24 V
Signal state L (Low)
-30 … +5 V
-30 … +5 V
Signal state H (High)
+15 … +32 V
+15 … +32 V
Input current (typical) H320
H322
7 mA
7 mA
7mA
2mA
Source operation (positive logic)
x
x
F
max
125 kHz
1)
125 kHz
1)
1)
Internal counting frequency 500 kHz
Encoder inputs for modules PCD2.H325 and PCD2.H32
7
Axis 1
Axis 2
Inputs
A,/A B,/B IN,/IN
A,/A B,/B IN,/IN
Number of inputs
6
6
Input voltage (typical)
RS-422
RS-422
Input impedance (typical) H325
H327
150 Ω
150 Ω
150 Ω
1500 Ω
F
max
250 kHz
1)
250 kHz
1)
1)
Internal counting frequency 1 MHz
5 V supply for 5 V encoder modules PCD2.H325 and PCD2.H327
Short circuit protection
Yes
Electrical isolation
No
Output voltage
5 V
Max. load current
300 mA
Short circuit current
400 mA
Overvoltage protection
TVS diode 39 V +/- 10 %
Reverse voltage protection
No
Power supply to all modules
Internal current consumption:
from +5 V bus (without encoder)
typically 210 mA, max. 230 mA
(250 mA in SSI operation)
Internal current consumption:
from V+ bus (without encoder)
15 … 20 mA
External current consumption:
0 … 2 mA (without load current)
1 A for outputs
Total current consumption for all I/O modules including encoders must not exceed
1.6 A. PCD2.H32x modules should be plugged onto the base unit wherever pos-
sible (not the expansion housing).
Operational conditions
Ambient temperature
operation: 0 … +55 °C without forced ventilation,
storage:
-20 … +85 °C
Noise immunity:
EC mark according to EN 61 000-6-3 and
EN 61 000-6-2
Programming:
Based on Saia PCD
®
user program and pre-
programmed function blocks (FB).
Terminals:
Pluggable 10-pole spring terminal block
(4 405 4847 0), for wires up to 1.5 mm²