PCD2.G200
Specifications
9
9.2.1
Resolution of the analogue inputs
Mode
Resolution [analogue]
Resolution
[digital]
Read Values
(default)
Voltage
0…+10 V
2.44 mV (linear)
1 mV
0…+10‘000
Current
0…+20 mA
5.14 uA (linear)
1 uA
0…+20‘000
Resistance
0…2'500 Ω
0.50…0.80 Ω
0.1 Ω
0...25’000
Resistance
0…300 kΩ
0…10 kΩ:
10 k…20 kΩ:
20 k…40 kΩ:
40 k…70
kΩ:
70 k…100 kΩ:
100 k…300 kΩ:
2…14 Ω
14…40 Ω
40…130 Ω
130…350 Ω
350…700 Ω
0.7…4.5 kΩ
1 Ω
0..300’000
Pt 1000
–
50…+400°C:
0.15…0.25°C
0.1°C
–
500…4000
Ni 1000
–
60…+200°C:
0.09…0.11°C
0.1°C
–
600…2000
Ni 1000 L&S
–
60…+200°C:
0.12…0.15°C
0.1°C
–
600…2000
Table 3:
Resolution of the module
9.2.2
Dip Switch position
The input circuit for the analogue inputs AI2 … AI5 can be selected by mini Dip
switches:
Figure 3: DIP Switches
The modes T (NI/PT1000), C (0…20 mA) or V (0…10 V) are selected by putting
the switch in the down position. Only one switch per channel has to be on, except
in the 0…
300 kΩ range where the T and the V switch must be on.
The above picture shows the default setting (all on T) where all inputs are config
-
ured in the temperature measurement mode.