Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
6-67
I/O modules PCD3
PCD3.W3x0
6
Digital/analogue values
Input signals and type
Digital values
PCD3.W300/W340
PCD3.W310/W340
PCD3.W340/50/60
Classic
xx7
Simatic
+ 10.0 V
+ 20 mA
Calculate the
appropriate values
with the formulae
at the end of this
section
4095
4095
27684
+ 5.0 V
+ 10 mA
2047
2047
13842
0 V
0 mA
0
0
0
for instructions, see section 6.1.5
E7 E6
E5 E4
E3
E2
E1 E0
T
V/4
V
C
T
V/4
V
C
T
V/4
V
C
T
V/4
V
C
T
V/4
V
C
Bus connector
Jumper for working
Mode selection
(PCD3.W340 only)
T
V/4
V
C
T
V/4
V
C
T
V/4
V
C
T
V/4
V
C
Position 'T': Pt/Ni 1000
Position 'V/4': (0 .. +2.5V)
Position 'V': 0 .. +10V
Position 'C': 0 .. 20 mA
Jumper positions for selecting working mode
PCD3.W340 only; on the other module types the working modes are fixed
All inputs set for temperature (position T) must be wired. All unused inputs (with the W340)
must be adjusted to current range ‘C’ or voltage range ‘V’.
Changing the jumpers
On this circuit board there are components that are sensitive to electrostatic discharges. For