I/O modules PCD3
PCD3.A810
6
LEDs and connection terminals
1 A 0
1 A 0
1 A 0
1 A 0
12
24V
11
GND
10
A0 nc
9
A0 co
8
A0 no
7
A1 nc
6
A1 co
5
A1 no
4
A2 co
3
A2 no
2
A3 co
1
A3 no
Pin 12 in front
PCD3.A810
4 rel. out 5/6
A
250 V
AC
A
8
1
0
12 11 10 9 8 7 6 5 4 3
A0
A1
A2
A3
+ –
24
VDC
2 1
LEDs
green: Automatic
yellow: Manual
red: Output
Description-
Label
Terminals
0
1
2
3
Man
Auto
Man
Control elements
Each channel has a toggle switch with three settings
Manual on, Auto, Manual off.
There are 2 LEDs fitted per channel:
The upper LED is two-colour and displays the operating mode for the channel:
amber = Manual; green = Automatic
The lower LED displays the switch state of the relay:
Red = relay activated.
Example (above):
Output 0:
Manual off
LED 1 = amber
Relay off
LED 2 = off
Output 1:
Manual on
LED 1 = amber
Relay on
LED 2 = red
Output 2:
Automatic
LED 1 = green
Relay off
LED 2 = off
Output 3:
Automatic
LED 1 = green
Relay on
LED 2 = red
If there is no external supply to the relay coils, the LED does not light up and the
relays are not activated.
There is no error message to the Saia PCD
®
where the electrical supply is not pres-
ent.