Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
7-5
PCD2.B160 & PCD3.B160
Hardware
7
7.2.6
Technical data on outputs
Number of outputs:
16, source operation, not isolated (in groups of 4)
Voltage range:
18…30 VDC
Output current:
250 mA per channel
Total module current:
2 A
Output delay (on/off):
typ. 2 μs
Inductive loads:
Transient Suppressor Diode 39 V
Short circuit proof:
Yes
7.2.7
Output wiring
I/O_0
I/O_2
I/O_4
I/O_6
GND
0
2
4
6
8
1
3
5
7
9
I/O_1
I/O_3
I/O_5
I/O_7
24V
X0 / X1
0 V
24 V
Load
The supply pins of each connector must be powered.
Be careful of the power polarity.
Fuse:
It is recommended that each supply connection should be separately protected with a
fast-blow (S) fuse. The value depends on the application.