Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
8-5
PCD2.W380 & PCD3.W380
PCD2/3.W380, 8 analog configurable inputs
8
8.1.3.2
Technical data of inputs
Each input can be configured to be used in the following modes:
Mode
Reso-
lution
[Bit]
Resolution [measure]
Accuracy
(@ T
Ambient
= 25°C)
Display
Voltage
–10 V
…
+10 V
12 +
Sign
2,44 mV (linear)
0,2 % of measured value ± 10 mV
–10‘000 …
+10‘000
R
IN
= 330 kΩ
Current
–20 mA …
+20 mA
12 +
Sign
5,39
μ
A (linear)
0,2 % of measured value ± 20 mV
–20‘000 …
+20‘000
R
SHUNT
= 225Ω
Resistance
0...2'500 Ω
12 bit
0,50
…
0,80 Ω
0,2 % of measured value ±
3 Ω
0 … 25’000
Measuring current: 1,0
…
1,3 mA
Resistance
13 bit
0
…
10 kΩ:
10 k
…
40 kΩ:
40 k
…
70 kΩ:
70 k
…
100 kΩ:
100 k
…
300 kΩ:
1
…
10 Ω
10
…
40 Ω
40
…
100 Ω
100
…
200 Ω
0,2
…
1,5 kΩ
0,2 % of measured value ±
40 Ω
0,2 % of measured value ±
160 Ω
0,5 % of measured value ±
400 Ω
1,0 % of measured value ±
800 Ω
2,5 % of measured value ±
5,0 Ω
0 … 300’000
Measuring current: 30 µA
…
1,3 mA
Pt 1000
12 bit
–50
…
+400 °C:
0,15
…
0,25 °C 0,2 % of measured value ±
0,5 Ω
–500 … 4000
Measuring current: 1,0
…
1,3 mA
Ni 1000
12 bit
–50
…
+200 °C:
0,09
…
0,11 °C 0,2 % of measured value ± 0,5 °C
–500 … 2000
Measuring current: 1,0
…
1,3 mA
Ni 1000 L&S
12 bit
–30
…
+130 °C:
0,12
…
0,15 °C 0,2 % of measured value ± 0,5 °C
–300 … 1300
Measuring current: 1,0
…
1,3 mA
Diode
0...5’000 mV
12 bit
1,22 mV (linear)
0,2 % of measured value ± 10 mV
0 … 5’000
Measuring current: 0,7
…
1,3 mA
Table 2: Inputs specifications for each mode
The measuring current was chosen to be the best compromise between the reso-
lution and the sensors self-heating effect, which is negligible for most of the sen
-
sors and applications. Even in bad measuring conditions with Pt/Ni1000 sensors
with a low thermal coupling as 4 mW/K, the maximal error produced by the sen-
sors self-heating is lower than 0.3°C.