Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-24
I/O modules PCD1|PCD2
PCD2.A300
5
5.4.1
PCD2.A300, 6 digital outputs for 2 A each
Application
Low cost output module with 6 transistor outputs 5 mA … 2 A, without short-circuit
protection. The individual circuits are electrically connected; the voltage range is
10 … 32 V
DC
.
Technical data
Number of outputs:
6, electrically connected
Output current:
5 mA …
2 A (leakage current max. 0.1 mA)
Total current per module:
6 × 2 A = 12 A (on 100 % duty cycle)
Operating mode:
Source operation (positive switching)
Voltage range:
10 …
32 VDC, smoothed
10 … 25 VDC, pulsed
Voltage drop:
0.2 V at 2 A
Output delay:
Switch-on delay <1 µs
Switch-off delay <200 µs
with inductive loads the delay is longer, because of the
protective diode.
Isolation voltage:
1000 VAC, 1 min
Resistance to interference:
acc. to IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling (whole trunk group)
Internal current consumption:
(from +5 V bus)
1 … 20 mA; typically 12 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption: Load current
Terminals:
Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²
LEDs and connection terminals
9
8
7
6
5
4
3
2
1
0
A0
A1
A2
A3
A4
A5
A5
A3
A1
A4
A2
A0
Bus connector
Bus interface
Output transistors (MOSFET)
Protective diodes
LEDs
Screw terminals
Outputs
Load supply