Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
6-21
I/O modules PCD3
PCD3.E61x
6
6.3.2
PCD3.E610/613, 8 digital inputs, electrically isolated from the I/O Bus
Application
Input module for source or sink operation with 8 inputs, electrically isolated
by optocoupler. Suitable for most electronic and electromechanical switching
elements at 24 V
DC
.
Technical data
Number of inputs:
8 electrically isolated by optocoupler,
source or sink operation,
all inputs to the model in the same phase
Input voltage
E610:
E613:
24 V
DC
(15…30 V
DC
) smoothed or pulsed
48 V
DC
(30…60 V
DC
) smoothed max. 10 % ripple
Supply voltage:
for source operation:
for sink operation:
E610: E613:
min.
15 V
30 V
min.
18 V
36 V
Input current:
(at input voltage)
for source operation:
for sink operation:
E610: E613:
(24
V
DC
) (48
V
DC
)
5 mA
2 mA
3.7 mA
1.5 mA
Input delay (0-1/1-0):
E610: E613:
incl.
10 ms
9 ms
excl.
10 ms
9 ms
Resistance to interference:
acc. to IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling
(whole trunk group)
Electrical isolation voltage:
Optocoupler isolation voltage:
1000 V
AC
, 1 min.
2.5 kV
Electrical isolation of outputs to the Saia PCD
®
.
The channels are not isolated from each other
Internal current consumption:
(from +5 V bus)
1
…
24 mA
typ. 12 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption:
max. 40 mA (all inputs=1) at 24 V
DC
, (source operation),
max. 18 mA (sink operation)
Terminals:
Plug-in 10-pole spring terminal block (4 405 4954 0) or
pluggable 10-pole screw terminal block (4 405 4955 0),
both for wires up to 2.5 mm²