98
Note
:
No matter set by key
or terminal UP/DOWN, the set value is added with a regulating variable based on F0.12 or
F0.13, and the final output frequency ranges from the lower limit to the maximum output value. The regulating variable
via terminal UP/DOWN can be cleared by choosing “UP/DOWN terminal frequency zero clearing” via X terminal, and the
regulating variable of keypad can be cleared by choosing “clear key
set of frequency” via key
M-FUNC
.
2: digital set 3 (communication set)
Modify the set frequency via serial port frequency set command, for details check FB group communication parameter.
3: AI1 analog set (0~10V/20mA)
The frequency setting is determined by analog voltage/current of AI1 terminal, and the input range DC 0~10V/20mA. The
relevant setting is in F6.00~F6.05.
4: AI2 analog set (0~10V)
Frequency setting is determined by analog voltage/current of AI2 terminal, input ranges DC 0~10V. The relevant setting is
in F6.06~F6.11.
5: impulse set
Frequency setting is determine by terminal impulse frequency (only input via X6, see F7.05). Input impulse signal
specification: high level range 15~30V; frequency range 0~50kHz. The relevant setting is in F6.15~F6.20.
6: simple PLC set
It needs to set function code F9.00~F9.05 to select this mode. Function code F9.00~F9.21 are used to determine the
running frequency of each PLC section, and F9.22~F9.53 are used to the increase/decrease time and running time of each
section.
7: multispeed running setting
The VFD runs in multispeed mode in this frequency setting mode. Set the F7 group “X terminal as multispeed” and F9
group “multispeed frequency” function code to determine the correspondence of specified section number and
frequency.
8: PID control setting