156
58
:
start/stop (manual)
When this terminal is valid, frequency is given by AI1, PID control is not conducted, and controlled by interlock signal.
The earlier input interlock signal will start first. If input together, start the one corresponding smaller number.
59
:
running allowed (X2)
This terminal is used to control start/stop of VFD, normally connecting signal of external water shortage or high
voltage.
60
:
interlock1 (X3)
This terminal connection corresponds relay R2 output.
61
:
interlock2 (X4)
This terminal connection corresponds relay R3 output.
62
:
interlock3 (X5)
This terminal connection corresponds relay R4 output.
63
:
PFC start/stop (X6)
When this terminal is valid, PID control is conducted, and controlled by interlock signal. The earlier input interlock
signal will start first. If input together, start the one corresponding smaller number.
64
:
A frequency switch B and run
65~99
:
reserved
F7.08
digital filtering times
1
~
10
5
This function is used to set sensitivity of input terminal. If digital input terminal is susceptible to interference so as to
cause error action, increase this parameter to improve the anti-interference ability, but overlarge value will result in a
lower sensitivity.
F7.09
Terminal function detection when powerup
0
~
1
0
0
:
terminal control invalid when powerup
During powering up, even detected that the terminal of operation command is valid (closed), the driver will not start;
only when the terminal closed again after disconnected, the driver will start.