165
32
:
auxiliary motor 2
The function of constant pressure water supply can be realized by auxiliary motor 1,2 and PID function module.
33
:
total operating time arrival
This signal is sent when the operating limit time (FC.11) arrives.
34
~
49
:
multi-speed or PLC running segment
The output terminal function 34
~
49 items correspond to 0
~
15 segments of multi-speed or simple PLC, and this
signal is sent when the corresponding segment of output terminal setting arrives.
50
:
VFD running indication
Indication signal output when VFD is in in forward/reverse running state.
51
:
temperature arrival indication
This signal is sent when actual temperature (d-33
~
d-34) is higher than threshold temperature (FA.14).
52
~
99
:
reserved
F7.22
Effective logic setting of output terminal (Y1
~
Y2)
0
~
3H
0
Bit0: effective logic definition of Y1 terminal
Bit1: effective logic definition of Y2 terminal
0
:
positive logic, i.e. Yi terminal is enabled when it connects with common terminal and disabled if disconnected.
1
:
negative logic, i.e. Yi terminal is disabled when it connects with common terminal and enabled if disconnected.
When F7.22=0, Yi and Y2 terminals are enabled when they connect with common terminal and enabled if disconnected.
When F7.22=1, Y1 terminal is disabled when it connect with common terminal and enabled if disconnected; Y2 terminal
is disabled when it connect with common terminal and enabled if disconnected.
When F7.22=2, Y1 terminal is enabled when it connect with common terminal and disabled if disconnected; Y2 terminal
is disabled when it connect with common terminal and enabled if disconnected.
When F7.22=3, Y1 and Y2 terminals are disabled when they connect to common terminal and enabled if disconnected.
F7.23
Frequency arrival of FAR detection range