153
24: VFD operating prohibiting
If this function is enabled, the drive that is operating will coast to stop and the drive ready to run will be prohibited to
start. This function is mainly used as safety protection.
25
:
switch operating command to keypad
When this terminal function is enabled, the operating command is switched to keypad control from present channel
forcibly. If the terminal is disconnected, the previous operating command channel will be enabled.
26
:
switch operating command to terminal
When this terminal function is enabled, the operating command is switched to terminal control from present channel
forcibly. If the terminal is disconnected, the previous operating command channel will be enabled.
27
:
switch operating command to communication
When this terminal function is enabled, the operating command is switched to communication control from present
channel forcibly. If the terminal is disconnected, the previous operating command channel will be enabled.
28
:
clear the setting of auxiliary frequency
This function is only valid for digital auxiliary frequency (F0.08=0, 1, 2) to clear it to zero, so that the reference
frequency is determined solely bay main reference.
29
:
switch from frequency source
A
to K*
B
When this terminal function is enabled, if F0.09 (frequency combinational algorithm) is set as 6, the frequency setting
channel is switched to frequency source B, and back to A when it is disabled.
30
:
switch from frequency source
A
to
A+
K*
B
When this terminal function is enabled, if F0.09 (frequency combinational algorithm) is set as 7, the frequency setting
channel is switched to frequency source (
A+
K*
B
), and back to A if it is disabled.
31
:
switch from frequency source
A
to
A
-K*
B
When this terminal function is enabled, if F0.09 (frequency combinational algorithm) is set as 8, the frequency setting
channel is switched to frequency source (
A
-K*
B
), and back to A if it is disabled.
32
:
reserved
33
:
PID control input
This terminal function is enabled when frequency is input via PID manually. Refer to F8 group parameter setting for
details.