When a fiber transceiver works, ensure that the port has been connected with a fiber or is covered with a dust cap so
as to keep out dust and avoid burning your eyes.
Do not stare into any fiber port.
Do not stare into any fiber port under any circumstances, as this may cause permanent damage to your
eyes.
Installation Site Requirements
RG-N18000 must be used in the room. To ensure normal operation and a prolonged useful life of the equipment, the
installation site must meet the following requirements.
Load Bearing Requirements
Evaluate the load bearing requirements for the ground according to the weight of the switch and its components (such as
the cabinet, chassis, single board and power supply). Make sure the installation site meet the requirements.
Space Requirements
It is recommended that the width of the machine room corridor be greater than 0.8m to ensure enough space for
moving of chassis and plugging and removing of modules.
Please do not install the switch against the wall. Instead, please leave some space around the switch for heat
dissipation and switch maintenance.
Ventilation Requirements
See
RG-N18014
and
RG-N18010
in
Product Overview
for their heat dissipation and ventilation respectively. Sufficient
space (10 cm at least) must be reserved at the air intakes and exhaust vents for ventilation. After connecting various
cables, you should bundle the cables or place them in the cable management bracket to avoid blocking air intakes.
Remove all foam packaging materials and protective plastics before you power on RG-N18014/RG-N18010.
Temperature Requirements
To ensure the normal operation and a prolonged useful life of the RG-N18000, you must maintain an appropriate
temperature in the equipment room. Too high or low temperature for a long period of time may damage the equipment.
In an environment with high temperature, the equipment is subjected to even greater harm, as its performance may
degrade significantly and its useful life may be shortened in the case of long-term exposure that expedites the aging
process.
Temperature Requirements of the RG-N18000
Operating Temperature
Storage Temperature
0ºC–50ºC
-40ºC to 70ºC
The ambient temperature is measured at the point that is 1.5m above the floor and 0.4m before the
equipment when there is no protective plate in front or back of the equipment rack.
Humidity Requirements
To ensure the normal operation and a prolonged use life of the RG-N18000, you must maintain an appropriate humidity in
the equipment room. Too high or low humidity for a long period of time may damage the equipment.
In an environment with high relative humidity, the insulating material may have bad insulation or even leak electricity,
and sometimes the materials may suffer from mechanical performance change and metallic parts may get rusted.