It is recommended that you do not insert the QSFP+ module with a fiber into the slot. Unplug the fiber before
installing the module.
Do not touch the connecting finger on the module.
Do not squeeze, bend or fold the optical fiber, which may cause system performance degradation or data loss.
Installing 40-Gigabit QSFP+ Cables
To avoid damaging components due to operation errors, read this section carefully before installing
40-Gigabit QSFP+ copper cables.
Take the following steps to install 40-Gigabit QSFP+ copper modules:
1)
You can install the QSFP+ copper module with power on. Hold the connector of a copper cable module with one
hand and carry the cable to the front panel of the switch with the other. Push the module gently into the QSFP+
module slot until you hear a click, indicating the module is correctly installed.
Figure 3-38 Installing the QSFP+ Copper Module
2)
After the cable is connected, the Link/ACT Status LED is on. Otherwise, please check the connector.
Precaution
If the QSFP+ copper module cannot be inserted to hit the back panel, do not push it forcefully. Please try the other
end of the module.
Do not touch the connecting finger on the module.
Do not squeeze, bend or fold the copper cable, which may cause system performance degradation or data loss.
After the cable is plugged, make sure that the bending radius is greater than 5 times of the cable diameter.
Too small bending radius may cause damage to the copper cable. For example. If the cable diameter is
7.4mm, the bending radius should be 35mm at least, as shown in figure 3-39:
Figure 3-39 Bending Radius and Cable Diameter