![Rockwell Automation PowerFlex 750-Series User Manual Download Page 99](http://html.mh-extra.com/html/rockwell-automation/powerflex-750-series/powerflex-750-series_user-manual_1475453099.webp)
DeviceNet Objects
C-5
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Instance Attributes
Attribute ID Access Rule Name
Data Type
Description
1
Get
Bad Flag
BOOL
If set to 1, then attribute 4 may contain invalid data.
0 = good
1 = bad
2
Get
Direction
BOOL
Direction of data transfer
0 = Producer Register (drive to network)
1 = Consumer Register (network to drive)
3
Get
Size
UINT
Size of register data in bits
4
Conditional
(1)
Data
ARRAY of BITS
Data to be transferred
(1)
The access rule of Set is optional if attribute 2, Direction = 1. If Direction = 0, the access rule is Get.