![Rockwell Automation PowerFlex 750-Series User Manual Download Page 83](http://html.mh-extra.com/html/rockwell-automation/powerflex-750-series/powerflex-750-series_user-manual_1475453083.webp)
Troubleshooting
7-5
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Viewing Option Module
Diagnostic Items
If you encounter unexpected communications problems, the Option
Module’s diagnostic items may help you or Rockwell Automation
personnel troubleshoot the problem. Option Module diagnostic items
can be viewed using the enhanced PowerFlex 7-Class HIM,
DriveExplorer software (version 6.01 or higher), or DriveExecutive
software (version 5.01 or higher). For details on viewing diagnostic
items using the HIM, refer to the Enhanced PowerFlex 7-Class HIM
User Manual (publication 20HIM-UM001).
Table 7.A Option Module Diagnostic Items
No. Name
Description
1
Common Logic Cmd The present value of the Common Logic Command being transmitted to the drive by this Option Module.
2
Prod Logic Cmd
The present value of the Product Logic Command being transmitted to the drive by this Option Module.
3
Reference
The present value of the Reference being transmitted to the drive by this Option Module.
4
Common Logic Sts
The present value of the Common Logic Status being received from the drive by this Option Module.
5
Prod Logic Sts
The present value of the Product Logic Status being received from the drive by this Option Module.
6
Feedback
The present value of the Feedback being received from the drive by this Option Module.
7
Input Size
The size of the input image in bytes transferred from the network to the drive.
8
Output Size
The size of the output image in bytes transferred from the drive to the network.
9
DL Fr Net Avail
The number of Host DL From Net xx Datalinks currently available to the Option Module.
10
DL To Net Avail
The number of Host DL To Net xx Datalinks currently available to the Option Module
11
DL Fr Net 01 Val
The present value of respective Host DL From Net xx parameter being transmitted to the drive by this
Option Module. (If not using a Datalink, its respective value should be zero.)
12
DL Fr Net 02 Val
13
DL Fr Net 03 Val
14
DL Fr Net 04 Val
15
DL Fr Net 05 Val
16
DL Fr Net 06 Val
17
DL Fr Net 07 Val
18
DL Fr Net 08 Val
19
DL Fr Net 09 Val
20
DL Fr Net 10 Val
21
DL Fr Net 11 Val
22
DL Fr Net 12 Val
23
DL Fr Net 13 Val
24
DL Fr Net 14 Val
25
DL Fr Net 15 Val
26
DL Fr Net 16 Val
27
DL To Net 01 Val
The present value of respective Host DL To Net xx parameter being received from the drive by this
Option Module. (If not using a Datalink, its respective value should be zero.)
28
DL To Net 02 Val
29
DL To Net 03 Val
30
DL To Net 04 Val
31
DL To Net 05 Val
32
DL To Net 06 Val
33
DL To Net 07 Val
34
DL To Net 08 Val
35
DL To Net 09 Val
36
DL To Net 10 Val
37
DL To Net 11 Val
38
DL To Net 12 Val
39
DL To Net 13 Val
40
DL To Net 14 Val
41
DL To Net 15 Val
42
DL To Net 16 Val
43
DPI Rx Errs
The present value of the DPI Receive error counter.
44
DPI Rx Errs Max
The maximum value (since reset) of the DPI Receive Error counter.
45
DPI Tx Errs
The present value of the DPI Transmit error counter.
46
DPI Tx Errs Max
The maximum value (since reset) of the DPI Transmit Error counter.
47
Net Rx Errs
The number of receive errors reported by the DeviceNet hardware.
Summary of Contents for PowerFlex 750-Series