![Rockwell Automation PowerFlex 750-Series User Manual Download Page 40](http://html.mh-extra.com/html/rockwell-automation/powerflex-750-series/powerflex-750-series_user-manual_1475453040.webp)
4-4
Configuring the I/O
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Figure 4.5
Scanner New Module Screen
5. Edit the following:
6. Click OK. The scanner is now added to the RSLogix 5000 project.
It appears in the I/O Configuration folder. In our example, a
1756-DNB scanner appears under the I/O Configuration folder
(
) with its assigned name. For convenience, keep the
project open. Later in this chapter the project will need to be
downloaded to the controller.
Figure 4.6
RSLogix 5000: I/O Configuration Folder
Box
Setting
Name
A name to identify the scanner.
Description
Optional – description of the scanner.
Node
The node address of the DeviceNet scanner.
Slot
The slot of the DeviceNet scanner in the rack.
Revision
The minor revision of the firmware in the scanner. (You already set the major
revision by selecting the scanner series in Step 3.)
Electronic
Keying
Compatible Module. The “Compatible Module” setting for Electronic Keying
ensures the physical module is consistent with the software configuration
before the controller and scanner make a connection. Therefore, ensure that
you have set the correct revision in this screen. Refer to the online Help for
additional information on this and other Electronic Keying settings.
Input Size
The size of the input data for the DeviceNet scanner. It is recommended to
use the default value of 124.
Output Size The size of the output data for the DeviceNet scanner. It is recommended to
use the default value of 123.
Status Size
The size of the status data for the DeviceNet scanner. It is recommended to
use the default value of 32.
Open
Module
Properties
When this box is checked, additional module properties screens will appear
to further configure the scanner after clicking OK. When unchecked, the
scanner’s New Module screen will close after clicking OK. For this example,
uncheck this box.