4-10
Configuring the I/O
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
9. Click the Scanlist tab to begin the drive I/O configuration. The
Available Devices window (left) shows devices that are presently
on the DeviceNet network but are not yet configured. The Scanlist
window (right) shows devices that are presently on the DeviceNet
network and are configured.
For this example, uncheck the Automap on Add box. Then select
the PowerFlex 755 drive in the Available Devices window and click
the > button to move it to the Scanlist window (
).
Figure 4.14 1756-DNB Scanlist Tab Screen
10. Click Edit I/O Parameters… to display the Edit I/O Parameters
screen (
) for the PowerFlex 755 drive used in this
example.
TIP: The Automap on Add box is checked by default and allows
RSNetWorx for DeviceNet to automatically map the drive I/O into
the scanner in the next available registers. The mapping is based on
the minimum I/O requirements (8 bytes for input and 8 bytes for
output) that the scanner obtains from the drive EDS file.
Box
Setting
Node Active
Activates/deactivates the scanlist in the 1756-DNB for the selected
device. For this example, keep the box checked.
Device Type
These Electronic Key category check boxes select how specific the
device in the scanlist must be for the 1756-DNB to match its
compatibility for I/O operation. The more boxes that are checked, the
more specific the device must be to operate. For this example, leave the
default boxes (Device Type, Vendor, and Product Code) checked.
Vendor
Product Code
Major Revision