Configuring the I/O
4-13
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Figure 4.17 1756-DNB Output Tab Screen
15. Click OK. If the Scanner Configuration Applet appears asking to
download these settings to the 1756-DNB, click Yes.
16. Click File > Save. If this is the first time you saved the project, the
Save As dialog box appears. Navigate to a folder, type a file name,
and click Save to save the configuration to a file on your computer.
17. When configuring the I/O for additional PowerFlex 750-Series
drives on the network, repeat Steps 9 through 16.
Important: When all Datalinks in each drive are used (18 DINTs of
I/O per drive), a maximum of 6 PowerFlex 750-Series
drives can be mapped. This is due to the amount of I/O
available in the 1756-DNB scanner, which is 124
DINTs maximum.