7-4
Troubleshooting
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
NET A Status Indicator
Status
Cause
Corrective Actions
Off
The Option Module and/or network
is not powered, or the Option
Module is not connected properly to
the network.
•
Securely connect and ground the Option
Module to the drive by fully inserting it into the
drive port and tightening its two captive
screws to the recommended torque.
•
Correctly connect the DeviceNet cable to the
Option Module’s DeviceNet plug.
•
Apply power to the drive.
•
Verify that the DeviceNet network is powered.
Solid
Red
The Option Module failed
duplicated node detection test or
bus off.
The node address switch setting is
invalid.
•
Configure the Option Module to use a unique
node address on the DeviceNet network.
•
Configure the Option Module to use the
correct network data rate.
•
Ensure network has correct media installed.
•
Verify that the node address switch setting is
between 0 and 63.
Flashing
Red
A DeviceNet I/O connection has
timed out.
•
Place the scanner in RUN mode, or apply
power to the peer device that will send I/O.
•
Check the amount of traffic on the network.
Flashing
Red/
Green
The Option Module has received an
Identify Comm Fault request.
Wait for the faulted node recovery to complete.
Flashing
Green
The Option Module is properly
connected but is not
communicating with any devices on
the network.
•
Place the controller in RUN mode.
•
Program a controller to recognize and
transmit I/O or make a messaging connection
to the Option Module.
•
Configure the Option Module for the program
in the controller.
Solid
Green
The Option Module is properly
connected and communicating on
the network.
No action required.