Configuring the I/O
4-15
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Downloading the Project to the Controller and Going Online
After adding the scanner and drive/adapter to the I/O configuration, you
must download the configuration to the controller. You should also save
the configuration to a file on your computer.
1. In the RSLogix 5000 window, select Communications >
Download. The Download dialog box (
) appears.
Figure 4.18 Download Dialog Box
2. Click Download to download the configuration to the controller.
When the download is successfully completed, RSLogix 5000 goes
into the Online mode and the I/O OK box in the upper-left of the
screen should be solid green.
3. Select File > Save. If this is the first time you saved the project, the
Save As dialog box appears. Navigate to a folder, type a file name,
and click Save to save the configuration to a file on your computer.
4. To ensure that the present project configuration values are saved,
RSLogix 5000 prompts you to upload them. Click Yes to upload
and save them.
5. Place the controller in Remote Run or Run Mode.
TIP: If a message box reports that RSLogix 5000 is unable to go
online, select Communications > Who Active to try to find your
controller in the Who Active screen. After finding and selecting the
controller, click Set Project Path to establish the path. If your
controller does not appear, you need to add or configure the
DeviceNet driver in RSLinx. Refer to the RSLinx online help.