2-6
Installing the Option Module
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Table 2.A Drive and Option Module Start-Up Status Indications
After verifying correct operation, swing down the drive HIM bezel to its
closed position and install the drive cover.
Configuring/Verifying Key Drive Parameters
The PowerFlex 750-Series drive can be separately configured for the
control and Reference functions in various combinations. For example,
you could set the drive to have its control come from a peripheral or
terminal block with the Reference coming from the network. Or you
could set the drive to have its control come from the network with the
Reference coming from another peripheral or terminal block. Or you
could set the drive to have both its control and Reference come from the
network.
Item Name
Color
State
Description
Drive STS Indicator
➊
STS
(Status)
Green
Flashing
Drive ready but not running, and no faults
are present.
Steady
Drive running, no faults are present.
Yellow
Flashing
When running, a type 2 (non-configurable)
alarm condition exists – drive continues to
run. When stopped, a start inhibit condition
exists and the drive cannot be started (see
drive parameter 933 - [Start Inhibits]).
Steady
A type 1 (user configurable) alarm condition
exists, but the drive continues to run.
Red
Flashing
A major fault has occurred. Drive will stop.
Drive cannot be started until fault condition
is cleared.
Steady
A non-resettable fault has occurred.
Red/Yellow
Flashing Alternately A minor fault has occurred. Use drive
parameter 950 - [Minor Flt Config] to enable.
If not enabled, acts like a major fault. When
running, the drive continues to run. System
is brought to a stop under system control.
The fault must be cleared to continue.
Yellow/Green Flashing Alternately When running, a type 1 alarm exists.
Green/Red
Flashing Alternately Drive is flash updating.
Option Module Status Indicators
➋
PORT
Green
Flashing
Normal Operation. The Option Module is
establishing an I/O connection to the drive.
It will turn solid green or red.
Steady
Normal Operation. The Option Module is
properly connected and communicating
with the drive.
➌
MOD
Green
Flashing
Normal Operation. The Option Module is
operating but is not transferring I/O data.
Steady
Normal Operation. The Option Module is
operating and transferring I/O data.
➍
NET A
Green
Flashing
Normal Operation. The Option Module is
properly connected but is not
communicating with any devices on the
network.
Steady
Normal Operation. The Option Module is
properly connected and communicating on
the network.
Summary of Contents for PowerFlex 750-Series
Page 143: ......