![Rockwell Automation PowerFlex 750-Series User Manual Download Page 26](http://html.mh-extra.com/html/rockwell-automation/powerflex-750-series/powerflex-750-series_user-manual_1475453026.webp)
3-2
Configuring the Option Module
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Using the HIM to Access
Parameters in the Option
Module
1. Display the Status screen, which is shown on HIM power up.
2. Use the
or
key to scroll to the Port in which the
DeviceNet Option Module is installed.
3. Press the PAR# soft key to display the Jump to Param # entry
pop-up box.
4. Use the numeric keys to enter the desired parameter number, or use
the
S
or
T
soft key to scroll to the desired parameter number.
Setting the Node Address
If the Data Rate switch (
) is set to position “3,” the value of
Device Parameter 07 - [Net Addr Cfg] determines the node address.
When the Data Rate switch is set to any other position, the Node
Address switches determine the node address. We recommend that you
do not use node address 63 because all new devices on the network use
this address as the default address. Also, node address 63 is used for
Automatic Device Recovery (ADR).
1. Set the value of Device Parameter 07 - [Net Addr Cfg] to a unique
node address.
Figure 3.1
Edit Net Address Cfg HIM Screen
2. Reset the Option Module; see
Resetting the Option Module on
The NET A status indicator will be solid green or flashing green if
the node address is correctly configured, and the Option Module is
connected to an operational network.
Setting the Data Rate
If the Option Module Data Rate switch (
) is set to position
“3” (Program), the value of Device Parameter 09 - [Net Rate Cfg]
determines the data rate. The Autobaud setting will detect the data rate
used on the network if another device is setting the data rate. Your
application may require a different setting.
1. Set the value of Device Parameter 09 - [Net Rate Cfg] to the data
rate at which your network is operating.