4-2
Configuring the I/O
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
5. When the Add New RSLinx Driver screen appears, type a name (if
desired) and click OK. The Configure Drivers screen reappears
with the new driver in the Configured Drivers list (
Figure 4.1
Configure Drivers Screen with a Configured Driver
6. Click Close to close the Configure Drivers screen. Leave RSLinx
running.
ControlLogix Example
Example Network
After the Option Module is configured, the connected drive and Option
Module will be a single node on the network. This section provides the
steps needed to configure a simple DeviceNet network (see
In our example, we will configure a ControlLogix controller with
1756-DNB scanner to communicate with a drive using Logic
Command/Status, Reference/Feedback, and 32 Datalinks (16 to read/16
to write) over the network.
Figure 4.2
Example ControlLogix DeviceNet Network
Adding the Scanner to the I/O Configuration
To establish communications between the controller and Option
Module over the network, you must first add the ControlLogix
controller and its scanner to the I/O configuration.
Node 0
ControlLogix Controller
with 1756-DNB Scanner
Node 1
PowerFlex 750-Series
Drive with 20-750-DNET
Option Module
Node 62
Computer with
DeviceNet Connection