Configuring the I/O
4-9
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Figure 4.12 1756-DNB Properties Screen
7. Click the Module tab to display the Scanner Configuration Applet
screen. Click Upload to upload the 1756-DNB configuration to the
RSNetWorx for DeviceNet project and display the 1756-DNB
Module Tab screen (
).
Figure 4.13 1756-DNB Module Tab Screen
8. Edit the following:
Then click Apply.
Box
Setting
Interscan Delay Sets the scanner time delay between consecutive I/O scans on the
network. For this example, it is recommended to leave the default setting
of 10 milliseconds. Note: When numerous drives are on the network and
the drives are faulting on a Comm Loss, increasing this value may help.
Foreground…
Sets the ratio of foreground to background polls. For this example, it is
recommended to leave the default setting of 2.
Slot
Sets the slot location in which the scanner is installed. For this example,
Slot 3 is selected.