3-6
Configuring the Option Module
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Using COS (Change of State) Data Exchange
1. Set Device Parameter 11 - [COS Status Mask] for the bits in the
Logic Status word that should be checked for changes. For the
Logic Status bit definitions, refer to
documentation.
2. To edit any of the bits, press the EDIT soft key to display the Edit
COS Status Mask screen.
Figure 3.5
Edit COS Status Mask HIM Screen
To toggle a bit between 0 or 1, press any numeric key except the
or
key.
3. Set Device Parameter 12 - [COS Fdbk Change] for the amount of
change to the Feedback that is required to trigger a Change of State
message.
Figure 3.6
Edit COS Fdbk Change HIM Screen
The Option Module is now configured for COS data exchange. You
must configure the scanner to allocate it using COS (
).
TIP: The HIM shows 32-bit Bit-type parameters in two 16-bit sets.
By default, the lower 16-bit set (bits 00-15) is shown. To view the
upper 16-bit set (bits 16-31), press the UPPER soft key. To view the
lower 16-bit set again, press the LOWER soft key. To select each bit
position, use the
W
or
X
soft key or the
or
numeric key.
Value Description
0
Ignore this logic bit. (Default)
1
Use this logic bit.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
W
X
Edit COS Status Mask
xxxx xxxx xxxx xxx
x
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit COS Fdbk Change
0.000
0.000 << 3.40282E38
EXP