D-6
Group Motor Installations
The rules and allowances for sizing of the over current protection for
NFPA 79 motor groups is covered by 7.2.10.4, Table 7.2.10.4 and
Table 13.5.6. These rules in Tables 7.2.10.4 and 13.5.6 are intended to
limit the maximum SCPD for a group. Therefore each ArmorStart
controller with its factory-supplied output motor cable is suitable for
single-motor or multiple-motor group installations on industrial
machinery when installed according to NFPA 79, 2002. The
controller and output motor cable have been evaluated as a single
system. The maximum over current device rating or setting is limited
to the value in Table D.1 for the smallest user-supplied input line
conductor, by the controller's maximum rating, or as allowed by the
UL Certificate of Compliances 012607-E3125, E96956, and E207834
for the combined use of ArmorStart and ArmorConnect components.
The Certificate of Compliances allow the ArmorStart Distributed
Motor Controllers Models 280*-*10*, 281*-*10*, and 284*-*10*
respectively to be used with ArmorConnect input cable media 280*-
PWRM22*-M*, 280S-PWRM22*-M* Cable Assembly branch
circuit taps, and 280*-M22*-M1 ArmorConnet Panel Mounting
Fittings when the group motor branch circuits are protected with a
maximum 40 A non-time delay or a 20 A time delay, Class CC, T or F
fuse.
These ArmorStart and ArmorConnect product UL Certification of
Compliances effectively extend Table D.1 to allow ArmorConnect
branch circuit taps and mounting fittings constructed with 16 AWG
conductor sized to be connected to appropriate ArmorStart motor
controllers. See Table D.1.
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Page 292: ...E 4 Accessories Notes ...
Page 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Page 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Page 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Page 323: ......