Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
4-13
Pr Fault Reset
This parameter resets the Protection Fault on a transition 0 > 1.
Parameter Number
25
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
StrtrDN FltState
This parameter in conjunction with Parameter 27 defines how the starter will
respond when a DeviceNet fault occurs. When set to 1, hold to last state occurs.
When set to 0, will go to DnFlt Value on DN faults as determined by Parameter 27.
Parameter Number
26
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
StrtrDN FltValue
This parameter determines if the starter will be commanded in the event of a
DevceNet fault.
0 = OFF
1 = ON
Parameter Number
27
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
StrtrDN IdlState
This parameter in conjunction with Parameter 29 defines how the starter will respond
when a DeviceNet network is idle. When set to 1, hold to last state occurs. When set
to 0, will go to DnFlt Value on DN faults as determined by Parameter 29.
0 = Go to Idle Value
1 = Hold Last State
Parameter Number
28
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
StrtrDN IdlValue
This parameter determines the state that starter assumes when the network is idle
and Parameter 28 is set to 0.
0 = OFF
1 = ON
Parameter Number
29
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Page 292: ...E 4 Accessories Notes ...
Page 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Page 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Page 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Page 323: ......