4-46
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Figure 4.6
Anlg In 0…10V Lo
Sets the analog input level that corresponds to parameter 134 (Minimum Freq) if a
0…10V input is used by parameter 138 (Speed Reference)
Parameter Number
210
Related Parameter
121, 134, 138, 222
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1%
Minimum Value
0.0%
Maximum Value
100.0%
Default Value
0.0%
Stop drive before changing this parameter.
Anlg In 0…10V HI
Sets the analog input level that corresponds to parameter 135 (Maximum Freq) if a
0…10V input is used by parameter 138 (Speed Reference). Analog inversion can be
accomplished by setting this value smaller than parameter 210 (Anlg In 0…10V Lo).
Parameter Number
211
Related Parameter
121, 135, 138, 222, 223
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1%
Minimum Value
0.0%
Maximum Value
100.0%
Default Value
0.0%
Anlg In4…20MA LO
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number
212
Anlg In4…20 mA HI
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number
213
0
Parameter 135
[Maximum Freq]
Parameter 134
[Minimum Freq]
Parameter 210
[Anlg In 0-10V Lo]
Parameter 211
[Anlg In 0-10V Hi]
0
Speed Reference
Stop drive before changing this parameter.
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Page 292: ...E 4 Accessories Notes ...
Page 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Page 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Page 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Page 323: ......