Bulletin 284G CIP Information
C-19
Discrete Output Point Object —
CLASS CODE 0x0009
The following class attributes are supported for the Discrete Output
Point Object:
Table C.44 Discrete Output Point Object Class Attributes
Ten instances of the Discrete Output Point Object are supported.
Table C.45 summarizes the DOP instances:
Table C.45 Discrete Output Point Object Instance Attributes
All instances will contain the following attributes
Table C.46 Discrete Output Point Instance Attributes.
➊
For DOP Instances 1 and 2, and 9 and 10, Attributes 113 and 114 have Get only access, and their
values are always 0
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
1
2
Get
Max Instance
UINT
10
Instance
ID
Name
Alternate
Mapping
Description
1
Run Fwd
Output
0029 – 01
– 03
Run Forward output. For all starter types, this output
is hard wired from the ArmorStart CPU to the
actuator
2
Run Rev
Output
0029 – 01
– 04
Run Reverse output. For all starter types, this output
is hard wired from the ArmorStart CPU to the
actuator
3
Reserved
none
4
Reserved
none
5
Drive Input 1
none
These four instances exist for Inverter units only.
They are connected to Drive Inputs 1…4.
6
Drive Input 2
none
7
Drive Input 3
none
8
Drive Input 4
none
9
Drive Jog
Fwd
none
This instances exists for Inverter units only
10
Drive Jog Rev
none
Attribute ID
Access Rule
Name
Data Type
Value
3
Get
Value
BOOL
0 = OFF, 1 = ON
5
Get/Set
Fault Action
BOOL
0 = Fault Value
attribute, 1 =
Hold Last State
6
Get/Set
Fault Value
BOOL
0 = OFF, 1 = ON
7
Get/Set
Idle Action
BOOL
0 = Fault Value
attribute, 1 =
Hold Last State
8
Get/Set
Idle Value
BOOL
0 = OFF, 1 = ON
113
Get/Set
➊
Pr Fault Action
BOOL
0 = Pr Fault Value
attribute, 1 =
Ignore
114
Get/Set
➊
Pr Fault Value
BOOL
0 = OFF, 1 = ON
115
Get/Set
Force Enable
BOOL
0 = Disable, 1 =
Enable
116
Get/Set
Force Value
BOOL
0 = OFF, 1 = ON
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...