4-40
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Brake Voltage
Sets the frequency where brake voltage is applied when Parameter 184 (Boost
Select) = 0 Custom V/Hz and Parameter 225 (Torque Perf Mode) = 0V/Hz.
Parameter Number
186
Related Parameters
131, 132, 134, 135, 184, 185,
187, 188, 225
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1.1%
Minimum Value
0.0%
Maximum Value
100.0%
Default Value
25.0%
Brake Frequency
Sets the frequency where brake frequency is applied when Parameter 184 (Boost
Select) = 0 Custom V/Hz and Parameter 225 (Torque Perf Mode) = 0V/Hz.
Parameter Number
187
Related Parameters
131, 132, 134, 135, 184, 185,
186, 188, 225
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 Hz
Minimum Value
0.0 Hz
Maximum Value
400.0 Hz
Default Value
15.0 Hz
Maximum Voltage
Sets the highest voltage the drive will output.
Parameter Number
188
Related Parameters
104, 185, 186, 187
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1V AC
Minimum Value
20V AC
Maximum Value
Drive Rated Volts
Default Value
Drive Rated Volts
Current Limit 1
Maximum output current allowed before current limiting occurs
Parameter Number
189
Related Parameters
133, 218
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 A
Minimum Value
0.1 A
Maximum Value
Drive rated amps X 1.8
Default Value
Drive rated amps X 1.5
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Page 292: ...E 4 Accessories Notes ...
Page 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Page 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Page 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Page 323: ......