4-30
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Table 4.3
155 (Relay Out Sel)
Sets the condition that changes the state of the output relay contacts.
Parameter Number
155
Related Parameters
133, 156, 192, 240…247,
250…257, 260, 261
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0
Maximum Value
22
Default Value
22
Options
Description
0
Ready/Fault
(Default)
Relay changes state when power is applied. This indicates the drive is ready for operation. Relay returns drive to
shelf state when power is removed or a fault occurs.
1
At Frequency
Drive reached commanded frequency.
2
MotorRunning
Motor is receiving power from drive.
3
Reverse
Drive is commanded to run in reverse direction.
4
Motor Overld
Motor overload condition exists.
5
Ramp Reg
Ramp regulator is modifying the programmed accel/decal times to avoid overcurrent or overvoltage fault from
occurring.
6
Above Freq
Drive exceeds the frequency (Hz) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set
threshold.
7
Above Cur
Drive exceeds the current (% Amps) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set
threshold.
8
Above DCVolt
Drive exceeds the DC bus voltage value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set
threshold.
9
Retries Exst
Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.
10
Above Anlg V
Option not valid for Bulletin 284G ArmorStart.
11
Logic In 1
An input is programmed as
Logic In 1
and is active.
12
Logic In 2
An input is programmed as
Logic In 2
and is active.
13
Logic In 1 & 2
Both Logic inputs are programmed and active.
14
Logic In 1 or 2
One or both Logic inputs are programmed and one or both is active.
15
StpLogic Out
Drive enters Step Logic step with Digit 3 of Command Word (Parameters 240…247).
16
Timer Out
Timer has reached value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.
17
Counter Out
Counter has reached value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.
18
Above PF Ang
Power factor angle has exceeded the value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set
threshold.
19
Anlg In Loss
Analog input loss has occurred. Program parameter 122 (Analog In Los) for desired action when loss occurs
20
ParamControl
Enables the output to be controlled over the network communications by writing to Parameter 156 (Relay Out
Level) (0 = Off, 1 = ON).
21
NonRec Fault
Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.
22
EM Brk Cntrl
EM Brake is energized. Program Parameter 260 (EM Brk Off Delay) and Parameter 262 (EM Brk On Delay) for
desired action.
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Page 292: ...E 4 Accessories Notes ...
Page 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Page 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Page 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Page 323: ......