Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
4-27
Stop Mode
Valid Stop Mode for the Bulletin 284G ArmorStart are the following:
0 =
Ramp, CF
Ramp to Stop.
Stop
command clears active fault.
1 =
Coast, CF
Coast to Stop.
Stop
command clears active fault.
2 =
DC Brake,CF
DC Injection Braking Stop.
Stop
command clears active fault.
3 =
DCBrkAuto, CF
DC injection Braking with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time) or
Drive shuts off if the drive detects that the motor is stopped.
Stop
command clears
active fault
4 =
Ramp
Ramp to Stop
5 =
Coast
Coast to Stop
6 =
DC Brake
DC Injection Braking Stop
7 =
DC BrakeAuto
DC Injection Stop with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time)
or
Drive shuts off if current limit is exceeded
8 =
Ramp
+
EM B, CF
Ramp to Stop with EM Brake Control.
Stop
command clears
active fault.
9 =
Ramp
+
EM Brk
Ramp to Stop with EM Brake Control.
Parameter Number
137
Related Parameters
136, 180, 181, 182, 205, 260,
261
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
—
Minimum Value
0
Maximum Value
9
Default Value
9
Speed Reference
Valid Speed References for the Bulletin 284G ArmorStart are the following:
1 = Internal Freq
2 = 0…10V Input
4 = Preset Freq
5 = Comm port
6 = Stp Logic
9 = Jog Freq
Note:
Option 2 must be selected when using 0…10V Analog Input.
Parameter Number
138
Related Parameters
101, 102, 112, 139, 140, 151,
152, 153, 154, 169,
170…173, 174…177, 210,
211, 213, 232, 240…247,
and 250…257
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
—
Minimum Value
0
Maximum Value
7
Default Value
5
Accel Time 1
Sets the rate of acceleration for all speed increases.
Parameter Number
139
Related Parameters
138, 140, 151, 152, 153, 154,
167, 170…173, 174…177,
and 240…247
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
0.1 sec
Minimum Value
0.0 sec
Maximum Value
600.0 sec
Default Value
10.0 sec
Maximum Freq
Accel Time
--------------------------------------
Accel Rate
=
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Page 292: ...E 4 Accessories Notes ...
Page 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Page 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Page 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Page 323: ......