4-42
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Clear a Type 1 Fault and Restart the Drive
1.
Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.
2.
Set Parameter 193 (AutoRstrt Delay) to a value other than 0.
Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault
without Restarting the Drive
1.
Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.
2.
Set Parameter 193 (AutoRstrt Delay) to 0.
Auto Rstrt Tries
Set the maximum number of times the drive attempts to reset a fault and restart.
Parameter Number
192
Related Parameter
155, 158, 161, 193
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1
Minimum Value
0
Maximum Value
9
Default Value
0
ATTENTION
!
Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not
use this function without considering applicable local,
national, and international codes, standards, regulations, or
industry guidelines.
Auto Rstrt Delay
Sets time between restart attempts when Parameter 192 (Auto Rstrt Tries) is set to a
value other than zero.
Parameter Number
193
Related Parameters
192
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 sec
Minimum Value
0.0
Maximum Value
300.0 sec
Default Value
1.0 sec
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Page 292: ...E 4 Accessories Notes ...
Page 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Page 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Page 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Page 323: ......