Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
4-33
Table 4.5
Analog Output Options
Note:
Only options 5…14, 16, 17, 19, and 20 are not valid options.
Analog Out Sel
Sets the analog output signal (0…10V). The output is used to provide a signal that is
proportional to several drives
Parameter Number
165
Related Parameters
135, 166
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
See Table for details
Minimum Value
Maximum Value
Default Value
Options
Output Range
Minimum Output
Value
Maximum Output Value A066
(Analog Out High)
DIP Switch Position
Related
Parameter
0
OutFreq 0…10
0…10V
0V = 0 Hz
P035 (Maximum Freq)
0…10V
101
1
OutCurr 0…10
0…10V
0V = 0 Amps
200% Drive Rated Output Current
0…10V
103
2
OutVolt 0…10
0…10V
0V = 0 Volts
120% Drive Rated Output Volts
0…10V
104
3
OutPowr 0…10
0…10V
0V = 0 kW
200% Drive Rated Power
0…10V
122
4
TstData 0…10
0…10V
0V = 0000
65535 (Hex FFFF)
0…10V
119
5
OutFreq 0…20
0…20 mA
0 mA = 0 Hz
P035 (Maximum Freq)
0…20 mA
101
6
OutCurr 0…20
0…20 mA
0 mA = 0 Amps
200% Drive Rated Output Current
0…20 mA
103
7
OutVolt 0…20
0…20 mA
0 mA = 0 Volts
120% Drive Rated Output Volts
0…20 mA
104
8
OutPowr 0…20
0…20 mA
0 mA = 0 kW
200% Drive Rated Power
0…20 mA
122
9
TstData 0…20
0…20 mA
0 mA = 0000
65535 (Hex FFFF)
0…20 mA
119
10
OutFreq 4…20
4…20 mA
4 mA = 0 Hz
P035 (Maximum Freq)
0…20 mA
101
11
OutCurr 4…20
4…20 mA
4 mA = 0 Amps
200% Drive Rated Output Current
0…20 mA
103
12
OutVolt 4…20
4…20 mA
4 mA = 0 Volts
120% Drive Rated Output Volts
0…20 mA
104
13
OutPowr 4…20
4…20 mA
4 mA = 0 kW
200% Drive Rated Power
0…20 mA
122
14
TstData 4…20
4…20 mA
4 mA = 0000
65535 (Hex FFFF)
0…20 mA
119
15
OutTorq 0…10
0…10V
0V = 0 Amps
200% Drive Rated FLA
0…10V
129
16
OutTorq 0…20
0…20 mA
0 mA = 0 Amps
200% Drive Rated FLA
0…20 mA
129
17
OutTorq 4…20
4…20 mA
4 mA = 0 Amps
200% Drive Rated FLA
0…20 mA
129
18
Setpnt 0…10
0…10V
0V = 0%
100.0% Setpoint Setting
0…10V
209
19
Setpnt 0…20
0…20 mA
0 mA = 0%
100.0% Setpoint Setting
0…20 mA
209
20
Setpnt 4…20
4…20 mA
4 mA = 0%
100.0% Setpoint Setting
0…20 mA
209
Analog Out High
Scales the maximum output value for parameter 165 source setting
Parameter Number
166
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
%
Minimum Value
0%
Maximum Value
800%
Default Value
100%
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Page 292: ...E 4 Accessories Notes ...
Page 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Page 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Page 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Page 323: ......