Appendix
A
Specifications
Bulletin 280G/281G
Electrical Ratings
UL/NEMA
IEC
Power Circuit
Rated Operation Voltage
380/220V…480/277V AC
380/220V…480/277V AC
Rate Insulation Voltage
600V
600 V
Rated Impulsed Voltage
4 kV
4 kV
Dielectric Withstand
2200V AC
2500V AC
Operating Frequency
50/60 Hz
50/60 Hz
Utilization Category
N/A
AC-3
Protection Against Shock
N/A
IP2X
Rated Operating Current Max.
2.5 A
5.5 A
16 A
Control
Circuit
Rated Operation Voltage
Safety Products only:
24V DC (+10%, -15%) A2 (should be grounded at voltage source)
120V AC (+10%, -15%) A2 (should be grounded at voltage source)
Rated Short Circuit
1 kA
SCPD
10 A circuit breaker or equivalent
Rate Insulation Voltage
250V
250V
Rated Impulsed Voltage
—
4 kV
Dielectric Withstand
1500V AC
2000V AC
Overvoltage Category
—
III
Operating Frequency
50/60 Hz
50/60 Hz
Short Circuit
Protection
SCPD Performance Type 1
Current Rating
Voltage
480Y/277V
0.5…2.5 A
Sym. Amps RMS
65kA
1.1…5.5 A
3.2…16 A
30kA
SCPD Fuses,
only fuse types: J, CC, and T
100 A maximum
SCPD UL 489 Circuit Breakers
100 A maximum
Safety Products Only
C10 Base: 100 A maximum
C25 Base: 60 A maximum
SCPD List
Size per NEC Group Motor
Power Requirements
Units
Non-Safety Products
Safety Products
Control Voltage
Volts
120V AC, 50/60 Hz
24V DC
Contactor (Pick Up)
Amps
0.58 plus the motor brake current
1.09
Contactor (Hold In)
Amps
0.08 plus the motor brake current
30
120V AC Brake (Pick Up)
Amps
—
motor brake pick-up current
120V AC Brake (Hold In)
Amps
—
motor brake hold-in current
Total Control Power (Pick Up)
VA (W)
70
(26)
Total Control Power (Hold In)
VA (W)
9
(7.2)
Input Ratings
Rated Operation Voltage
24V DC
Input On-State Voltage Range
10…26V DC
Input On-state Current
3.0 mA @ 10V DC
7.2 mA @ 24V DC
Input Off-state Voltage Range
0…5V DC
Input Off-state Current
<1.5 mA
Input Filter — Software Selectable
Off to On
Settable from 0…64 ms in 1 ms increments
On to Off
Settable from 0…64 ms in 1 ms increments
Input Compatibility
N/A
IEC 1+
Number of inputs
6
Sensor Source
Voltage Status Only
11…25V DC from DeviceNet™
Current Available
50 mA MAX per Input, 300 mA Total
Summary of Contents for ArmorStart Bulletin 280G
Page 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Page 2: ......
Page 18: ...1 8 Product Overview Notes ...
Page 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Page 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Page 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Page 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Page 54: ...2 36 Installation and Wiring Notes ...
Page 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Page 157: ...Explicit Messaging on DeviceNet 6 7 ...
Page 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Page 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Page 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Page 210: ...10 22 Troubleshooting Notes ...
Page 224: ...A 14 Specifications Notes ...
Page 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Page 292: ...E 4 Accessories Notes ...
Page 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Page 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Page 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Page 323: ......