Rockwell Automation Publication IASIMP-QS005H-EN-P - April 2016
167
Safety System Application Guide
Chapter 6
Digital Guard I/O Module Faceplate Output Status View
The Guard I/O Faceplate Output Status view operates identically to the Input Status view except it does not have
Demand associated with it.
The following table provides the indicator descriptions, color codes, and required actions.
Code (hex)
Error Content
Probable Cause
Recommended Action
01
Configuration invalid
The configuration is invalid.
Configure the module correctly.
02
Over current detected
Trouble with the connected device.
Replace the connected device.
03
Short-circuit detected
Ground fault of the output signal line.
Check the wiring.
04
Output ON error
1. The power source (positive side) is in contact with the output
signal line.
2. Trouble with the internal circuit.
1. Check the wiring.
2. Replace the module.
05
Error in the other dual channel output
Dual channels are set and an error occurred in the other channel. Remove the error in the other channel.
06
Internal-relay output circuit error
Trouble with the internal circuit (1791DS-IB4XOW4 module
only).
Replace the module.
07
Relay error
Trouble with the relay
(1791DS-IB4XOW4 module only).
Replace the relay.
08
Output data error
Wrong setting for output data.
Check the program.
09
Short-circuit detected in output
Short-circuit between output signal lines.
Check the wiring.
Indicator
Color
Description
Action Required
State
Gray
De-energized (OFF)
None
Orange
Energized (ON)
None
Red
Faulted
Clear the Input/Output (device) fault.
Cycle
Gray
Input/Output not faulted.
None
Red
Input/Output faulted.
Clear the Input/Output (device) fault.
Cycle Input/Output.
Press Fault Reset.
Press Safety Reset.