INSTALLATION
Installation Instructions for SIS Bus Bar Systems A2MS001EN revision R05
74 / 130
4.7.1.3.3
EARTHING THE INDOOR
CONNECTION SLEEVE
Performing Earthing
…………………….
WARNING!
Risk of Injury and Material Damage from
Improper Procedure when Installing!
If the connection sleeve is trodden on during
installation, this can cause material damage. This, in
turn, can cause damage during operation, which can
lead to injuries and even death.
Never stand or tread on the connection sleeve
during installation.
Personnel:
Installation Staff
Protective Equipment:
Occupational Safety Clothing
Protective Gloves
Safety Footwear
Fig. 71: Earthing on the flange
1.
Attach the earthing as per the installation
drawing (Fig. 71).
2.
Tighten the earthing with a bolted connection
M10 (Fig. 71). See Appendix B for tightening torque.
3.
Check whether the connection is friction locked.
4.
Mark the checked bolted earthing connection