INSTALLATION
Installation Instructions for SIS Bus Bar Systems A2MS001EN revision R05
58 / 130
Preparing the flexible connectors
……
Personnel:
Installation staff
Protective Equipment:
Occupational safety clothing
Safety goggles
Protective gloves
Safety footwear
Cleaning
…………………………………...
Fig. 37: Cleaning flexible connectors
1.
Clean the contact areas of the flexible connectors
with a grinding fleece, and remove any dust with
acetone and a lint-free rag (Fig. 37).
2.
Clean the rest of the flexible connectors with a
lint-free rag.
Applying contact grease compound
….
Fig. 38: Applying contact grease compound
3.
Apply a small amount layer of PFISTERER
contact grease compound P1 to the contact areas (Fig.
38).
Fig. 39: Spreading the contact grease
compound
4.
Use a clean brush to spread the contact grease
compound to form a thin, even layer (Fig. 39). Make
sure all contact surfaces, top and bottom, on both
sides, are covered.