INSTALLATION
Installation Instructions for SIS Bus Bar Systems A2MS001EN revision R05
44 / 130
Fig. 13: Installing the bracket
3.
Fit the insulation plate (Fig. 13/2) underneath the
bracket (Fig. 13/1).
4.
Install the bracket (Fig. 13/1) with the insulation pipe
(Fig. 13/3), conical spring washer (Fig. 13/4) and nut (Fig.
13/5) as per the respective installation drawing.
Fig. 14: Bracket installed
The insulation pipe is made of brittle material.
Therefore, if necessary, the bolted connection
between the bracket and the C-profile may need to
be loosened so that the insulation pipe can be
centered tension-free. In the process, the system
has to be secured to prevent it from sagging, using
ratchet slings (for example).
Fig. 15: Tightening the nuts
5.
Tighten the nuts with the respective stipulated
torque as per the information on the packaging or the
package leaflet.
Fig. 16: Carrying out an insulation test
6.
Check that the insulation is intact with a continuity
test (
Fehler! Verweisquelle konnte nicht gefunden w
erden.
).