INSTALLATION
Installation Instructions for SIS Bus Bar Systems A2MS001EN revision R05
80 / 130
4.7.2.1.3
PREPARING THE
CONNECTION SLEEVE
PIPE
Personnel:
Installation staff
Protective Equipment:
Occupational safety clothing
Protective gloves
Safety footwear
Materials:
Acetone
Lint-free rag or paper towel
NOTICE!
Risk of Material Damage due to Improper
Cleaning!
Dust or metal particles in the connection sleeves can
cause flashovers. This can compromise safe operation
of the overall system.
– Clean all components properly before installation.
Principally, the outdoor connection sleeve only differs
from the indoor connection sleeve in that it has an
additional stainless steel pipe and the associated
additional earthing (
/1).
Fig. 84: Inside view of connection sleeve
pipe
1.
Use acetone and a lint-free rag to thoroughly
clean the inside of the connection sleeve pipe (Fig. 84).
2.
Use acetone and a lint-free rag to thoroughly
clean the outside of the connection sleeve, especially
the sealing surfaces.