10.3.3 Checking the ionisation current
1. Check the ionisation current at full load and at part load.
See
Manual for the control panel.
The value is stable after 1 minute.
2. Clean or replace the ionisation/ignition electrode if the value is lower
than 4 µA.
10.3.4 Checking the flue gas discharge/air supply connections
1. Check the flue gas discharge and air supply connections for condi
tion and tightness.
10.3.5 Checking the combustion
Combustion is checked by measuring the O
2
/CO
2
percentage in the flue
gas outlet duct.