Quinta Ace
160
Nominal input (Qn) for central heating operation (Hs) G31 (Propane)
min. - max.
kW
43.4 - 169.6
Full load central heating efficiency (Hi) (80/60°C) (92/42/EEC)
%
97.5
Full load central heating efficiency (Hi) (50°C/30°C) (EN15502)
%
103.6
Low load central heating efficiency (Hi) (return temperature 60°C)
%
98.4
Part load central heating efficiency (92/42/EEC) (return temperature
30°C)
%
108.5
(1) Factory setting.
Tab.4
Gas and flue gas data
Quinta Ace
160
Gas inlet pressure G20 (H gas)
min. - max.
mbar
17 - 25
Gas inlet pressure G31 (propane)
min. - max.
mbar
37 - 50
Gas consumption G20 (H gas)
(1)
min. - max.
m
3
/h
3.4 - 16.5
Gas consumption G31 (propane)
(1)
min. - max.
m
3
/h
1.4 - 6.3
BREEAM NO
X
mg/kWh
36
Flue gas mass flow rate
min. - max.
kg/h
g/s
57 - 277
16 - 77
Flue gas temperature
min. - max.
°C
32 - 66
Maximum counter pressure
Pa
200
(1) Gas consumption based on lower heating value under standard conditions: T=288.15 K, p=1013.25 mbar. Gag 30.33; G25 29.25; G31
88.00 MJ/m
3
Tab.5
Central heating circuit data
Quinta Ace
160
Water content
l
17
Water operating pressure
min
bar
0.8
Water operating pressure (PMS)
max
bar
4.0
Water temperature
max
°C
110
Operating temperature
max
°C
90
Pressure drop secondary circuit (ΔT=20 K)
mbar
170
Tab.6
Electrical data
Quinta Ace
160
Supply voltage
VAC
230
Power consumption – full load
max
W
275
Power consumption – low load
min
W
47
Power consumption – standby
min
W
5.3
Electrical protection index
IP
IPX1B
Fuses
Main
PCU
A
A
6.3
1.6
3 Technical specifications
7625116 - v.04 - 17012017