Tab.12 Air supply pipework materials
Version
Material
Single-wall, rigid
Aluminium
Plastic
Stainless steel
Flexible
Aluminium
Plastic
Stainless steel
6.5.4
Length of the air and flue gas pipes
Important
When using bends, the maximum chimney length (L) must be
shortened according to the reduction table.
The boiler is also suitable for longer chimney lengths and diam
eters other than those specified in the tables. Contact us for
more information.
Room-ventilated version (B
23
, B
23P
, B
33
)
Connecting the flue gas outlet
Connecting the air supply
With a room-ventilated version, the air supply opening stays open; only the
flue gas outlet opening is connected. This will ensure that the boiler ob
tains the necessary combustion air directly from the installation area. Use
adapters when using air supply and flue gas outlet pipes with diameters
other than 150 mm.
Caution
The air supply opening must stay open.
The installation area must be equipped with the necessary air
supply openings. These openings must not be obstructed or
shut off.
If the boiler is operated in a dusty environment (e.g. during the
construction phase), use of an air inlet filter is necessary.
Tab.13 Maximum chimney length (L)
Diameter
90 mm
100 mm 110 mm 130 mm 150 mm
Quinta Ace 160
5 m
8 m
15 m
37 m
40 m
(1)
(1) With retention of the maximum flue length it is possible to apply an extra 5
times 90º or 10 times 45º elbows.
Fig.16
Room-ventilated version
AD-0000220-01
L =