Tab.7
Other data
Quinta Ace
160
Total weight (empty)
kg
147
Minimum mounting weight (without front panel)
kg
123
Average acoustic level at a distance of one metre from the boiler
dB(A)
59.5
Tab.8
Technical parameters
Quinta Ace
160
Condensing boiler
Yes
Low-temperature boiler
(1)
No
B1 boiler
No
Cogeneration space heater
No
Combination heater
No
Rated heat output
Prated
kW
152
Useful heat output at nominal heat output and high temperature opera
tion
(2)
P
4
kW
152.1
Useful heat output at 30% of rated heat output and low temperature re
gime
(1)
P
1
kW
50.8
Seasonal space heating energy efficiency
ƞ
s
%
-
Useful efficiency at rated heat output and high temperature regime
(2)
ƞ
4
%
87.8
Useful efficiency at 30% of rated heat output and low temperature re
gime
(1)
ƞ
1
%
97.8
Auxiliary electricity consumption
Full load
elmax
kW
0.275
Part load
elmin
kW
0.047
Standby mode
P
SB
kW
0.005
Other items
Standby heat loss
P
stby
kW
0.191
Ignition burner power consumption
P
ign
kW
-
Annual energy consumption
Q
HE
kWh
GJ
-
Sound power level, indoors
L
WA
dB
68
Emissions of nitrogen oxides
NO
X
mg/kWh
35
(1) Low temperature means 30°C for condensing boilers, 37°C for low temperature boilers and 50°C (at heater inlet) for other heating appli
ances.
(2) High temperature operation means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
See
Refer to the back cover for contact details.
3 Technical specifications
14
7625116 - v.04 - 17012017