Room-sealed version (C
13
, C
33
, C
43
, C
63
, C
93
)
Connecting the flue gas outlet
Connecting the air supply
With a room-sealed version, both the flue gas outlet and the air supply
openings are connected (concentrically). Use adapters when using air
supply and flue gas outlet pipes with diameters other than 100/150 mm.
Tab.14 Maximum chimney length (L)
Diameter
100/150 mm
130/200 mm
150/220 mm
Quinta Ace 160
1 m
12 m
20 m
(1)
(1) Retaining the maximum chimney length, it is possible to use an extra 5 x
90º or 10 x 45º elbows.
Connection in different pressure zones (C
53
, C
83
)
Connecting the flue gas outlet
Air supply connection
Combustion air supply and flue gas discharge are possible in different
pressure areas and semi-CLV systems, with the exception of the coastal
area. The maximum permitted height difference between the combustion
air supply and the flue gas outlet is 36 m.
Tab.15 Maximum chimney length (L)
Diameter
90 mm
100 mm 110 mm 130 mm 150 mm
Quinta Ace 160
-
-
9 m
27 m
40 m
(1)
(1) With retention of the maximum flue length it is possible to apply an extra 5
times 90º or 10 times 45º elbows.
Reduction table
Tab.16 Pipe reduction for each element used (parallel)
Diameter
90 mm
100 mm
110 mm
130 mm
150 mm
250 mm
300 mm
45° bend
1.3 m
1.4 m
1.5 m
1.0 m
1.2 m
2.0
2.4
90° bend
4.5 m
4.9 m
5.4 m
1.8 m
2.1 m
3.5
4.2
Tab.17 Pipe reduction for each element used (concentric)
Diameter
100/150 mm
130/200 mm
150/220 mm
45° bend
1.0 m
1.5 m
1.5 m
90° bend
2.0 m
3.0 m
3.0 m
Fig.17
Room-sealed version
AD-0000219-01
L =
Fig.18
Different pressure zones
AD-0000114-01
L =
+
6 Installation
30
7625116 - v.04 - 17012017