Parameter
Text display
Adjustment range
160
AP006
The appliance will report low water pressure below this
value
0 bar - 7 bar
0.7
AP008
The appliance will wait x sec (0=off) for the release
contact to close in order to start the burner
0 Sec - 255 Sec
0
AP009
Burning hours before raising a service notification
0 Hours - 131070 Hours
17400
AP010
The type of service needed based on burn and
powered hours
0 = No service notification
1 = Custom service notification
2 = ABC service notification
2
AP011
Hours powered to raise a service notification
24 Hours - 131070 Hours
17400
AP073
Outdoor temperature: upper limit for heating
1.5 °C - 60 °C
22
AP074
The heating is stopped. Hot water is maintained. Force
Summer Mode
0 = Off
1 = On
0
AP079
Inertia of the building used for heat up speed
0 - 255
0
AP080
Outside temperature below which the antifreeze
protection is activated
-32 °C - 10 °C
0
AP102
Configuration of the boiler pump as zone pump or
system pump (feed lowloss header)
0 = No
1 = Yes
0
AP110
Parameter to activate the 2nd return sensor
0 = Inactive
1 = Active
0
CP000
Maximum Flow Temperature setpoint zone
0 °C - 90 °C
90
CP010
Zone flow temperature setpoint, used when the zone is
set to a fixed flow setpoint.
0 °C - 90 °C
80
CP020
Functionality of the zone
0 = Disable
1 = Direct
2 = Mixing Circuit
3 = Swimming pool
4 = High Temperature
5 = Fan Convector
6 = Domestic Hot Water tank
7 = Electrical Domestic Hot Water
8 = Time Program
9 = ProcessHeat
10 = Domestic Hot Water Layered
11 = Domestic Hot Water Boiler Internal
tank
1
CP060
Wished room zone temperature on holiday period
5 °C - 20 °C
6
CP070
Max RoomTemperature limit of the circuit in reduced
mode, that allows switching to comfort mode
5 °C - 30 °C
15
CP200
Manually setting the RoomTemperature setpoint of the
zone
5 °C - 30 °C
20
CP210
Comfort footpoint of the temperature of heat curve of
the circuit
15 °C - 90 °C
15
CP220
Reduced footpoint of the temperature of heat curve of
the circuit
15 °C - 90 °C
15
CP230
Heating curve temperature gradient of the zone
0 - 4
2.5
CP240
Adjustment of the influence of the zone room unit
0 - 10
3
CP340
Type of Reduced Night Mode, stop or maintain heating
of circuit
0 = Stop heat demand
1 = Continue heat demand
0
CP470
Setting of the screed drying program of the zone
0 Days - 30 Days
0
CP480
Setting of the start temperature of the screed drying
programm of the zone
20 °C - 50 °C
20