Parameter
Text display
Adjustment range
160
CP490
Setting of the stop temperature of the screed drying
programm of the zone
20 °C - 50 °C
20
CP670
Configuration of pairing room unit per zone
-
CP780
Selection of the control strategy for the zone
0 = Automatic selection on control strategy
1 = Room temperature control
2 = Outdoor temperature control
3 = Outdoor temperature control with room
inlfluence
1
DP010
Hysteresis for burner start in DHW mode
0 °C - 60 °C
7
DP011
Offset for burner stop in DHW mode
0 °C - 60 °C
5
DP015
Hysteresis on flow temperature setpoint in Combi DHW
mode
0 °C - 60 °C
0
DP016
Offset on flow temperature setpoint in Combi DHW
mode
0 °C - 60 °C
0
DP056
Prortional gain for process heat control on Central
Heating
0 - 255
50
DP211
Integral gain for process heat control on Central
Heating
0 - 255
20
EP014
Smart Control Board function 10 Volt PWM input
0 = Off
1 = Temperature control
2 = Power control
0
GP010
Gas Pressure Switch check on/off
0 = No
1 = Yes
0
GP021
Modulate back when delta temperature is large then
this treshold
5 °C - 25 °C
25
GP022
Tau factor for average flow temperature calculation
0 - 255
1
GP024
Valve Proofing System check on / off
0 = No
1 = Yes
0
PP007
Minimum burner anticycling time
0 Min - 20 Min
3
PP012
Time at partial load after burner start
5 Sec - 180 Sec
30
PP015
Central heating pump post run time; 99 = Pump non
stop.
1 Min - 99 Min
1
PP016
Maximum central heating pump speed (%)
20 % - 100 %
100
PP018
Minimum central heating pump speed (%)
20 % - 100 %
20
PP023
Hysteresis to start burner in heating mode
1 °C - 25 °C
10
Tab.27 Factory settings G20 (H-gas)
Parameter
Text display
Adjustment range
160
DP003
Maximum fan speed on Domestic Hot Water
1000 Rpm - 8500 Rpm
6700
GP007
Maximum fan speed during Central Heating mode
1000 Rpm - 8500 Rpm
6700
GP008
Minimum fan speed during Central H Domestic Hot
Water mode
900 Rpm - 8500 Rpm
1900
GP009
Fan speed at appliance start
900 Rpm - 5000 Rpm
2200
9 Settings
7625116 - v.04 - 17012017
47